HPRWG1-12F

HPRWG1-12F

It is installed in high-voltage side of the distribution transformer or the Support Link of the distribution line as Transformers and lines short circuit, overload protection, and open, co-load struja.
Detalji od Proizvod:

 

Drop-out osigurač i pull the load drop-out fuse is is vanjski visokonapon zaštita of električni. It is installed in high-voltage side of the distribution transformer or the Support Link of the distribution line as Transformers and lines short circuit, overload protection, and open, co-load struja. Drop-out fuse is made by the the insulating bracket and fuse tubes, static contact is installed at both ends of the insulation bracket, Moving contact installed on both ends of fuse tube, Fuse tube is composed by inner arc tube and outer phenolic paper tube or epoxy glass cloth tube. Pull load drop-out fuse can enhance flexibility auxiliar contacts and arc chute for open, co-load current.

When drop-out fuse in the normal operation, the fuse tube with fuse tension to form the closed position. When the system fails, the fault current blown fuse quickly, And form of arc, arc tube by the electric arc burning, Decompose large amounts of gas, formed a high pressure in the tube, and formed vertical wind along the pipeline, The arc was quickly stretch and elongated. After fuse blows, the moving contact lose tension and turned out, locking mechanism, release fuse tube, fuse tube drop, formed breaking Position. When pull the load, use insulating rod to pull the moving contact. At this point, the moving and the static contact is still contact. Continued pull the contact with the insulating rod, the auxiliary contacts are separated. the arc appear between the auxiliary contacts, and was stretch in the hood slit, the arc cover has gas, when the current is 0, the arc goes out.

 

 

Ovo proizvod je korišteno 10 ~ 35KV distribucija linije grananje linije linije i distributori transformatori primarni strana, For preopterećenje i kratki krug zaštita Separacija i Kombinacija the ocijenjeno opterećenje struja.

The product model by JB/T8321-1996《Method of type AC high-voltage fuses express prepared. Product parameters made by GB15166.3-1994 《high voltage fuses Expulsion fuses express standards. The standards are not clearly defined the important parameters and configuration, Accord to JB/DQ2139-1986《10 ~ 35KV outdoor high voltage drop fuse interim technology express requires correction.

 

Uvjeti od Upotreba:

 

Ambijent temperatura: not viša than +40 degree , not less than -30 degree

Nadmorska visina: not prekorače 1000m (1000m above can be corrected GB311.1-1997)

Snaga frekvencija: 50 ± 2Hz

Potres intenzitet: 7 stupnjeva ispod

Maksimalno vjetar brzina: 35m/s

 

Tehnički parametri:

 

12KV-15KV

product-808-116

 

Popularni tagovi: hprwg1-12f, China hprwg1-12f proizvođači, Dobavljači, Tvornica, AM je osigurač, vanjski osigurač, dugački osigurač, osigurač otporan na eksploziju, Primarni osigurač, osigurač otporan na vrijeme